CDU coolant maintenance

Updated 22 October 2026 · Independent, sourced reference

Quick answer

Maintaining a CDU secondary loop means regularly checking glycol concentration, pH, conductivity, inhibitor level, particulates and microbiological growth, keeping filters clean, and topping up only with the same approved fluid. Numeric limits vary by fluid and hardware vendor and are not published here. Use your supplier's datasheet and your CDU manual.

Key takeaways

  • Use the supplier's limits. We don't publish generic numbers.
  • Concentration drifts with water top-ups.
  • Filtration protects microchannel cold plates.
  • Never mix fluid brands without supplier approval.
  • Many suppliers offer sampling programs.

Monitoring checklist

ParameterWhyTool
Glycol concentrationFreeze, microbial and corrosion protectionRefractometer
pHInhibitor healthMeter or strips
ConductivityContamination, inhibitor depletionMeter
Inhibitor levelCorrosion protectionLab analysis
ParticulatesCold-plate cloggingFilters, lab
MicrobesBiofilmLab / dip slides
Server rack cold plate on GPUcold plate on CPU CDUpump · filter · heat exchanger Facility waterto chillers / dry coolers warmcool Technology cooling loop (e.g. PG25)Facility loop
Direct-to-chip cooling: the PG25 or water-based coolant stays in a closed technology loop; the CDU passes heat to the facility water loop.

Routine tasks

  1. Log the readings on the supplier's schedule.
  2. Inspect and change the filters.
  3. Top up with the same pre-diluted fluid.
  4. Send samples for lab analysis as advised.
  5. Act on trends, not just on limits.

Common mistakes

  • Topping up with water. It dilutes the inhibitors.
  • Mixing brands.
  • Ignoring slow conductivity rise.

Sampling best practice

  • Sample from a point with active flow, after flushing the sample valve.
  • Use clean, supplier-provided bottles.
  • Label each sample with the loop, date and time.
  • Ship promptly for lab analysis.
  • Compare results with the baseline and trends.

Responding to out-of-range results

FindingTypical response (confirm with supplier)
Low concentrationTop up with fluid, not water; find the dilution source
Rising conductivityCheck for contamination or inhibitor depletion
ParticulatesInspect and replace filters; look for corrosion sources
Microbial growthSupplier-guided treatment or fluid replacement

What ASHRAE TC9.9 says to monitor

ASHRAE TC9.9 technical bulletins on TCS fluids say that, at a minimum, operators should measure and monitor pH, conductivity, glycol concentration and inhibitor reserve, and they also list turbidity, particulates and dissolved oxygen among the parameters to verify. For water-based TCS loops, ASHRAE's guidance calls for a pH of 8.0–9.5, required corrosion inhibitors and biocide, bacteria below 100 CFU/mL, and conductivity between 0.2 and 20 µmho/cm. For a glycol product, the supplier's datasheet limits govern.

ParameterFWS (facility side)TCS (IT side)
pH7 to 98.0 to 9.5
Corrosion inhibitor(s)RequiredRequired
BiocideNot specifiedRequired
Sulfide<10 ppm<1 ppm
Sulfate<100 ppm<10 ppm
Chloride<50 ppm<5 ppm
Bacteria<1000 CFU/mL<100 CFU/mL
Total hardness (as CaCO3)<200 ppm<20 ppm
ConductivityNot specified0.2 to 20 µmho/cm
Total suspended solidsNot specified<3 ppm
Residue after evaporation<500 ppm<50 ppm
Turbidity<20 NTU<20 NTU

Values as reproduced in the ASHRAE TC9.9 water-cooled servers white paper (Table 1, citing ASHRAE 2014 Tables 5.3 and 6.2). These are water-quality guidelines for water-based loops. A glycol fluid such as PG25 should be managed to its supplier's own limits, which may differ.

Cleaning, flushing and commissioning

Many TCS problems start before the first fill. ASHRAE bulletin guidance is to build with clean, non-contaminating materials, then perform controlled flushing and filtration before the final fill, using flush water that meets the TCS water-quality guidelines or ASTM D1193 Type II, and to verify cleanliness through fluid testing. The OCP PG25 guideline likewise devotes sections to cleaning, flushing, commissioning and filtration. Debris left from fabrication, such as flux, oils or particles, can foul microchannel cold plates and consume inhibitors early.

Building a maintenance log

RecordWhy
Date, loop ID, sample pointTraceability
pH, conductivity, glycol %Trend detection
Inhibitor reserve (lab)Corrosion protection remaining
Filter differential pressure and changesContamination load
Top-up volume and fluid lotDilution and leak tracking
Actions takenAudit trail for warranty discussions

See who makes data-center and car coolants

Browse suppliers →

Who does what

  • Facilities team: FWS water treatment, the CDU primary side.
  • CDU vendor or service partner: CDU operation, filters, alarms.
  • Fluid supplier: sampling program, lab analysis, treatment advice (several suppliers list such services; see Ecolab).
  • IT owner: hardware approvals and warranty conditions.

Warning signs between scheduled samples

  • Filter differential pressure rising faster than usual
  • Unexplained top-up volume (possible leak or weeping fitting)
  • Discoloration or cloudiness in sight glasses or samples
  • Rising conductivity trend in CDU telemetry
  • Flow or pressure alarms on specific racks (possible cold-plate fouling)

Investigate trends early. Inhibitor depletion and fouling are much easier to correct before cold plates are affected.

Spare fluid on site

Keep sealed containers of the same pre-diluted fluid, from a known lot, for top-ups. Store them per the SDS, and note the shelf life on the label.

Bottom line

Monitor the ASHRAE minimum parameters, follow supplier limits, and act on trends.

ASHRAE water-quality guidance: facility side vs IT side

ASHRAE TC9.9 stresses applying the facility water (FWS) table to building loops and the much stricter technology cooling system (TCS) table to IT-side loops. Mixing them up is, according to its water-cooled servers white paper, a common and costly error. The figures below are for water-based loops. Glycol products follow their supplier's limits.

ParameterFWS (facility side)TCS (IT side)
pH7 to 98.0 to 9.5
Corrosion inhibitor(s)RequiredRequired
BiocideNot specifiedRequired
Sulfide<10 ppm<1 ppm
Sulfate<100 ppm<10 ppm
Chloride<50 ppm<5 ppm
Bacteria<1000 CFU/mL<100 CFU/mL
Total hardness (as CaCO3)<200 ppm<20 ppm
ConductivityNot specified0.2 to 20 µmho/cm
Total suspended solidsNot specified<3 ppm
Residue after evaporation<500 ppm<50 ppm
Turbidity<20 NTU<20 NTU

Values as reproduced in the ASHRAE TC9.9 water-cooled servers white paper (Table 1, citing ASHRAE 2014 Tables 5.3 and 6.2). These are water-quality guidelines for water-based loops. A glycol fluid such as PG25 should be managed to its supplier's own limits, which may differ.

Short checklist

  • Readings logged
  • Filters checked
  • Same fluid for top-ups

More questions answered

Can sampling be automated?

Some CDUs monitor conductivity and other parameters. Lab analysis still adds detail.

Frequently asked questions

How often should data center coolant be tested?

Per your fluid supplier's program.

Can I top up PG25 with water?

Not unless the supplier says so. Use the same pre-diluted fluid.

Sources

  1. Dow: DOWFROST LC 25 product page
  2. Ecolab: coolants for direct liquid cooling
  3. ASHRAE TC9.9 white paper: Water-Cooled Servers: Common Designs, Components, and Processes
  4. ASHRAE TC9.9 Technical Bulletin (TCS cleaning and commissioning)
  5. ASHRAE TC9.9 Technical Bulletin (TCS fluid monitoring)
  6. OCP: Guidelines for Using Propylene Glycol-Based Heat Transfer Fluids in Liquid Cooled Racks (Rev 2.0, Sep 2026)